Downloading Configuration
To download configuration to the module, follow these steps:
1. Make sure the serial communication cable is connected between
the PC com port and the scanner serial port.
2. Verify that the processor is in Program mode.
3. Use the SST PROFIBUS configuration tool to connect to the
master.
4. You may be notified about a configuration mismatch between
what is in the scanner and your current PROFIBUS project.
Choose YES to retain your configuration.
A. Right-click on the
master to see the
pull-down menu.
B. Click on Connect.
Click on OK to retain
your configuration.