Analog input data format, Configuring analog input module – Rockwell Automation 1790D-NOV2/TNOV2 CompactBlock LDX Analog Modules User Manual
Page 41

Publication 1790-UM001A-EN-P - March 2002
Module Data, Status, and Channel Configuration for Analog Input Modules 3-7
Analog Input Data Format
Analog input data is presented as raw/proportional. The full 12-bit
resolution is used over the entire span of the input full scale range, as
shown in Table 3.1.
Configuring Analog Input
Module
Configuring CompactBlock LDX modules is as easy as POINT and
click. RSNetWorx for DeviceNet™ allows you to simply identify the
network and configure the I/O modules with easy-to-use Electronic
Data Sheets (EDS). Just POINT to the field and click on your selection.
To obtain EDS files for use in configuration, go to:
http://www.ab.com/networks/eds.
EDS files for blocks with matching catalog numbers (for D-Shell and
terminal block versions) are the same. Thus on the website or in
RSNetWorx for DeviceNet, there may be only one catalog number
listed for both versions.
When using 3rd-party configuration software, simply load the EDS
files into the software and follow the vendor’s instructions.
Table 3.1
Module:
Input Full Scale
Range:
HEX Data Range:
Decimal Data
Range:
Input Resolution:
1790D-N4V0/-TN4V0
0-10V dc
0000-0FFF
0-4095
2.44mV
1790D-N4C0/-TN4C0
4-20mA
0000-0FFF
0-4095
3.90
µ
A
0-20mA
0000-0FFF
0-4095
4.88
µ
A