HSSL Wiring

Connect the HSSL to establish communication between the primary and
secondary systems. Maximum cable length for the HSSL is 4.5 m (15 ft.).

Local Status Link Wiring

If you have more than one 1747-BSN module in the chassis, connect the LSL in
series between modules in the same chassis. This enables BSN modules in the
same chassis to exchange status information in order to perform switchovers in
unison.

RIO Link Wiring

The backup scanner module is connected to other devices on the RIO link in a
daisy-chain (serial) configuration. There are no restrictions governing the space
between devices, provided the maximum cable distance is not exceeded.

A ½ watt terminating resistor must be attached across lines one and two at each
end of the RIO link. The value of the resistor depends on the baud rate and
extended node capability, as shown in the table that follows.

Note: To use extended node, all devices on the RIO link must support it. Refer

to each device’s user manual.

Baud Rate

Max. Cable Distance

(Belden™ 9463)

Resistor Size

Using

Extended Node

Capability

57.6K baud

3048 m (10,000 ft.)

82

Ω 1/2 Watt

Gray-Red-Black-Gold

115.2K baud

1524 m (5,000 ft.)

230.4K baud

762 m (2,500 ft.)

Not Using

Extended Node

Capability

57.6K baud

3048 m (10,000 ft.)

150

Ω 1/2 Watt

Brown-Green-Brown-Gold

115.2K baud

1524 m (5,000 ft.)

230.4K baud

762 m (2,500 ft.)

82

Ω 1/2 Watt

Gray-Red-Black-Gold