10

Backup Scanner Module

Publication 1747-5.38

Figure 5

DIP Switch Locations

Configuration Switch

The six-position Configuration DIP Switch is used to select the baud rate,
configure the communication channel, and identify each individual BSN module
and the last BSN module. The tables below define the DIP switch configuration
settings.

DIP Switch

Position

Definition

Setting

1 and 2

Set the communication channel baud rate.

see the table on
page 11

3

Channel configuration.

DH+ = ON
RIO = OFF

4

This user identification switch differentiates between BSN
modules in the primary system and BSN modules in the
secondary system, helping determine if switchover has
occurred.

User selectable

5

Reserved.

6

Identifies the last module in the local status link.

Last module = ON
All others = OFF

1 2 3 4

O

N

1 2 3 4 5 6

O

N

1 2 3 4

1 2 3 4 5 6

Configuration Switch