Rockwell Automation 1738-VHSC24M23 ArmorPoint 24V dc Very High Speed Counter Module, Series A User Manual
Page 18
Publication 1738-IN011B-EN-E - August 2013
18 ArmorPOINT 24V DC Very High Speed Counter Modules, Series A
General Specifications (continued)
Dimensions
(HxWxD)
31.75 x 66.80 x 107.95 mm
(1.25 x 2.63 x 4.25 in.)
Temperature, Operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20...60°C (-4...140°F)
Temperature, Nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
-40...85°C (-40...185°F)
Relative Humidity
IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):
5...95% noncondensing
Shock, Operating
IEC60068-2-27 (Test Ea, Unpackaged Shock):
30 g
Shock, Nonoperating
IEC60068-2-27 (Test Ea, Unpackaged Shock):
50 g
Vibration
IEC60068-2-6 (Test Fc, Operating):
5 g @ 10...500Hz
ESD Immunity
IEC 61000-4-2:
6 kV contact discharges
8 kV air discharges
Radiated RF Immunity
IEC 61000-4-3:
10V/m with 1 kHz sine-wave 80% AM from 80...2700 MHz
10V/m with 200 Hz 50% Pulse 100% AM from 900...1890 Mhz
EFT/B Immunity
IEC 61000-4-4:
±2 kV @ 5 kHz on signal ports
Surge Transient Immunity
IEC 61000-4-5:
±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports
Conducted RF Immunity
IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80MHz
Emissions
CSPR 11:
Group 1, Class A
Enclosure Type Rating
Meets IP65/66/67 (when marked)
Mounting Base Screw Torque
#8 screw:
0.847 Nm – Aluminum
1.807 Nm – Steel
Weight (approx.)
0.289 kg
(0.637 lb.)
Wiring Category
2
2 - on signal ports