beautypg.com

Rockwell Automation 1738-VHSC24M23 ArmorPoint 24V dc Very High Speed Counter Module, Series A User Manual

Page 18

background image

Publication 1738-IN011B-EN-E - August 2013

18 ArmorPOINT 24V DC Very High Speed Counter Modules, Series A

General Specifications (continued)

Dimensions

(HxWxD)

31.75 x 66.80 x 107.95 mm

(1.25 x 2.63 x 4.25 in.)

Temperature, Operating

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

-20...60°C (-4...140°F)

Temperature, Nonoperating

IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),

IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),

-40...85°C (-40...185°F)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged Nonoperating Damp Heat):

5...95% noncondensing

Shock, Operating

IEC60068-2-27 (Test Ea, Unpackaged Shock):

30 g

Shock, Nonoperating

IEC60068-2-27 (Test Ea, Unpackaged Shock):

50 g

Vibration

IEC60068-2-6 (Test Fc, Operating):

5 g @ 10...500Hz

ESD Immunity

IEC 61000-4-2:

6 kV contact discharges

8 kV air discharges

Radiated RF Immunity

IEC 61000-4-3:

10V/m with 1 kHz sine-wave 80% AM from 80...2700 MHz

10V/m with 200 Hz 50% Pulse 100% AM from 900...1890 Mhz

EFT/B Immunity

IEC 61000-4-4:

±2 kV @ 5 kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5:

±1 kV line-line (DM) and ±2 kV line-earth (CM) on signal ports

Conducted RF Immunity

IEC 61000-4-6:

10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80MHz

Emissions

CSPR 11:

Group 1, Class A

Enclosure Type Rating

Meets IP65/66/67 (when marked)

Mounting Base Screw Torque

#8 screw:

0.847 Nm – Aluminum

1.807 Nm – Steel

Weight (approx.)

0.289 kg

(0.637 lb.)

Wiring Category

2

2 - on signal ports