16 ArmorPOINT 24V DC Very High Speed Counter Modules, Series A
Indication
Probable Cause
Network Status
Off
Device is not online:
– Device has not completed dup_MAC-id test.
– Device not powered. Check module status indicator.
Flashing Green
Device is online but has no connections in the established state.
Green
Device is online and has connections in the established state.
Flashing Red
One or more I/O connections in timed-out state.
Red
Critical link failure – failed communication device. Device
detected error that prevents it from communicating on the
network.
Flashing Red/Green
Communication faulted device – the device has detected a
network access error and is in communication faulted state.
Device has received and accepted an Identity Communication
Faulted Request - long protocol message.
Indication
Probable Cause
I/O Status
Input Status
Off
Input inactive
Yellow
Input is active and under control
Flashing Yellow
Input is toggling on and off
Output Status
Off
Output inactive
Yellow
Output is active and under control
Flashing Yellow
Output is toggling on and off
Flashing Red
Output is faulted (open, short, or no output power)
Flashing Red/Yellow
Output is toggling and faulted (possibly open)