1769-L32C, 1769-L35CR CompactLogix Controller 39
Publication
1769-IN070C-EN-P - May 2008
I/O
Off
Either of the following:
• There are no devices in the I/O configuration
of the controller.
• The controller does not contain a project
(controller memory is empty).
Steady green
The controller is communicating with all the devices in
its I/O configuration.
Flashing green
One or more devices in the controller’s I/O
configuration are not responding.
Flashing red
The controller is not communicating to any devices.
The controller is faulted.
OK
Off
No power is applied.
Flashing red
If a new controller, the controller requires a firmware
update.
If not a new controller, a major fault occurred. To clear
the fault, either:
• turn the keyswitch from PROG to RUN to PROG.
• go online with RSLogix 5000 software.
Steady red
Controller detected a nonrecoverable fault and cleared
the project. Follow these steps to recover:
1. Cycle power to the chassis.
2. Download the project.
3. Change to Run mode.
If the OK status indicator remains solid red, contact
your Rockwell Automation representative or
local distributor.
Steady green
Controller is OK.
Flashing green
The controller is storing or loading a project to or from
nonvolatile memory.
Controller Status Indicators
Indicator
Status
Description