Cyclic hart input data – Rockwell Automation 1794-IE8H, Series B FLEX I/O 8 Input Hart Analog Module Installation Instructions User Manual
Page 17
FLEX I/O 8 Input HART Analog Module 17
Publication
1794-IN108D-EN-P - January 2014
Cyclic HART Input Data
The HART input data holds the primary variables for the "live" HART
device, and other information gathered during the normal HART scan.
Additional "documentary" data is available through the pass through message
interface in the device information tables. Pass through messages are defined
in detail in the User Manual.
IMPORTANT
The HART Input Data for a channel may be zeroes if HART communications is
disabled for that channel. For more information on disabling HART
communications, refer to the Disable HART communications and HART
Disable functions in the Configuration Map table.
HART Input Data
Word
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
Reserved
Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0
(HART Communications Status)
1
Reserved
2
Ch0 HART Field Device Status
Ch0 HART Comm Status
3
Reserved
Ch0 HART Loop Status
4
Ch0 HART Primary Value
(IEEE 754-1985 Single-Precision 32 bit floating point)
5
6
Ch0 HART Secondary Value
(IEEE 754-1985 Single-Precision 32 bit floating point)
7
8
Ch0 HART Tertiary Value
(IEEE 754-1985 Single-Precision 32 bit floating point)
9
10
Ch0 HART Fourth (Quaternary) Value
(IEEE 754-1985 Single-Precision 32 bit floating point)
11
12
Ch0 Secondary Value Units Code
Ch0 Primary Value Units Code
13
Ch0 Fourth Value Units Code
Ch0 Tertiary Value Units Code
14
Ch1 HART Field Device Status
Ch1 HART Communication Status
15
Reserved
Ch1 HART Loop Status
16
Ch1 HART Primary Value
17