Troubleshooting your 1747-sdn scanner module, Troubleshooting your 1747ćsdn scanner module – Rockwell Automation 1771-SDN/B INSTL.INSTR.DEVICENET SEMINAR User Manual

Page 22

background image

DeviceNet Seminar Installation Instructions

22

Publication 1787Ć5.5 - December 1995

7. To save the EDS file you’ve just created,

choose

You see this warning message.

8. To save the EDS file, choose

You return to this screen.

9. Complete steps 1 through 8 for node 03, (SMP-3 overload relay).

The bicolor (green/red) module status indicator (MODULE)
displays module status. It indicates whether the module has power
and is functioning properly.

If the indicator is

Then

Take this action

Off

There is no power applied to

the module.

Apply power.

Green

The module is operating in

normal condition.

Do nothing.

Flashing Green

The module is not

configured.

Configure the module.

Flashing Red

There is an invalid

configuration.

Check configuration setup.

Red

The module has an

unrecoverable fault.

Replace the module.

top part of module

DeviceNet

STATUS

MODULE NET

ADDRESS/ERROR

module

status

indicator

network

status

indicator

Troubleshooting Your

1747ĆSDN Scanner Module