Troubleshooting your 1747-sdn scanner module, Troubleshooting your 1747ćsdn scanner module – Rockwell Automation 1771-SDN/B INSTL.INSTR.DEVICENET SEMINAR User Manual
Page 22
DeviceNet Seminar Installation Instructions
22
Publication 1787Ć5.5 - December 1995
7. To save the EDS file you’ve just created,
choose
You see this warning message.
8. To save the EDS file, choose
You return to this screen.
9. Complete steps 1 through 8 for node 03, (SMP-3 overload relay).
The bicolor (green/red) module status indicator (MODULE)
displays module status. It indicates whether the module has power
and is functioning properly.
If the indicator is
Then
Take this action
Off
There is no power applied to
the module.
Apply power.
Green
The module is operating in
normal condition.
Do nothing.
Flashing Green
The module is not
configured.
Configure the module.
Flashing Red
There is an invalid
configuration.
Check configuration setup.
Red
The module has an
unrecoverable fault.
Replace the module.
top part of module
DeviceNet
STATUS
MODULE NET
ADDRESS/ERROR
module
status
indicator
network
status
indicator
Troubleshooting Your
1747ĆSDN Scanner Module