Setting the Power Loss Time Delay(1771ĆP5E only)

Power loss time delay is the time period from when the power
supply input voltage drops below 20.5V dc to when the power
supply resets the processor enable signal on the I/O backplane.
When this signal is reset, the resident PLC

processor or adapter

module stops processing data to/from the modules in the I/O chassis.

You set the configuration jumper as follows:

Set the jumper

to this position

For this power loss

time delay

JPR1 Ċ Standard

(factory default position)

13.6 ms

±

3.6 ms

JPR2 Ċ Extended

60 ms

If your input modules and power supply use power from the same
source and the input module time delay is greater than the power loss
time delay of the power supply module, input module data integrity
is preserved. If using 2 power supplies, do not exceed the specified
isolation voltage (see Specifications).

!

ATTENTION

Exercise care when you configure your system for
possible power loss. You should consider:

input module time delay

power loss time delay

incoming power quality

control system response to input information