beautypg.com

Specifications – Rockwell Automation 1771-P3_P4_P5_P5E Power Supply Modules Installation Instructions User Manual

Page 18

background image

Power Supply Modules

18

Publication 1771ĆIN073A-EN-P - March 2002

1771ĆP3

1771ĆP4

1771ĆP5

1771ĆP5E

Module Location

1 slot in a 1771

I/O chassis

2 adjacent slots in a 1771 I/O chassis

Nominal Input Voltage/Current

0.42A, 120V ac

0.88A, 120V ac

3.0A, 24V dc

Input Voltage Range

97 to 132V ac rms

20.5 to 30V dc

Input Power

23 Watts

57 Watts

57 Watts

Frequency Range

50/60Hz

Not applicable

Isolation Voltage

Tested to 2160V dc for 1s

Output Voltage

5.06(+3.8%)V dc

Output Current

3A @ 5V dc maximum

8A @ 5V dc maximum

8A @ 5V dc maximum

Fuse

1A 125V slow blow

Bussman MDL1.0

Littelfuse 313001

IEC 127 Type T (blue)

1.5A 125V slow blow

Bussman MDX1.5

Littelfuse 31301.5

IEC 127 Type T (blue)

5A 32V normal blow

Bussman MTH5

Littelfuse 312005

IEC 127 Type M(yellow)

Power Dissipation

8W maximum

4W maximum @ 2A

7W maximum @ 4A

12W maximum @ 6A

17W maximum @ 8A

Adjacent Slot Power Dissipation

10W maximum

Terminal Block Screw Torque

7 pound-inches (0.5Nm)

Conductors

Wire Size

Insulation

Category

14AWG (2.5mm

2

) copper wire rated at 60

o

C or

greater

3/64 inch (1.2mm) insulation maximum

1

1

14AWG (2.5mm

2

) copper wire rated at 60

o

C or

greater

3/64 inch (1.2mm) insulation maximum

2

1

Branch Circuit Protection

15A maximum, user supplied

Power Loss Time Delay - Input

Power Loss to Processor Disable

13.6(+3.6ms)ms

Adjustable

13.6(+3.6ms)ms or 60ms

Environmental Conditions

Operating Temperature IEC 60068-2-1 (Test Ad, Operating Cold)

IEC 60068-2-2 (Test Bd, Operating Dry Heat)

IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

32 to 140

°

F (0 to 60

°

C)

Storage Temperature

IEC 60068-2-1 (Test Ab, Unpackaged, Nonoperating Cold)

IEC 60068-2-2 (Test Bb, Unpackaged, Nonoperating Dry Heat)

IEC 60068-2-14 (Test Na, Unpackaged, Nonoperating Thermal Shock)

-40 to 185

°

F (-40 to 85

°

C)

Relative Humidity

IEC 60068-2-30 (Test Db, Unpackaged, Nonoperating Damp Heat)

5 to 95%, noncondensing

Enclosure Type Rating

None (open style)

Weight

1.6 lbs (0.73 kg)

2.3 lbs (1.04 kg)

2.6 lbs (1.18 kg)

Paralleling Cable

Cat. No. 1771ĆCT

Keying - right hand slot

Between 12 and 14

Between 18 and 20

Between 12 and 14

Between 20 and 22

Between 12 and 14

Between 22 and 24

External Transformer (if used)

60VA

150VA

Not applicable

Specifications