Input specifications – Rockwell Automation 1769-IF4FXOF2F Compact Combination Fast Analog I/O Module User Manual
Page 26
![background image](/manuals/579378/26/background.png)
26 Compact Combination Fast Analog I/O Module
Publication 1769-IN081A-EN-P - February 2007
Input Specifications
Attribute
Value
Analog Normal Operating
Ranges
(1)
(1)
The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will
continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the
normal operating range.
Voltage: ± 10V dc, 0 to 10V dc, 0 to 5V dc, 1 to 5V dc
Current: 0 to 20 mA, 4 to 20 mA
Full Scale Analog Ranges
(1)
Voltage: ± 10.5V dc, -0.5 to 10.5V dc, -0.5 to 5.25V dc, 0.5 to 5.25V dc
Current: 0 to 21 mA, 3.2 to 21 mA
Number of Inputs
Four differential or single-ended
Converter Type
Successive Approximation
Response Speed per Channel
Input filter and configuration dependent. See your user’s manual.
Resolution (max.)
(2)
(2)
Resolution is dependent upon your filter selection.
14 bits (unipolar)
14 bits plus sign (bipolar)
Rated Working Voltage
(3)
(3)
Rated working voltage is the maximum continuous voltage that can be applied at the input terminal, including the input
signal and the value that floats above ground potential (for example, 10V dc input signal and 20V dc potential above
ground).
30V ac/30V dc
Common Mode Voltage Range
(4)
(4)
For proper operation, both the plus and minus input terminals must be within ±10V dc of analog common.
±10V dc maximum per channel
Common Mode Rejection
greater than 70 dB at 50 and 60 Hz with the 10 Hz filter selected,
respectively.
Input Impedance
Voltage Terminal: 220K
Ω (
typical)
Current Terminal: 250
Ω
Overall Accuracy
(5)
(5)
Includes offset, gain, non-linearity and repeatability error terms.
Voltage Terminal: 0.15% full scale at 25 °C
Current Terminal: 0.2% full scale at 25 °C