Rockwell Automation 1769-IF4FXOF2F Compact Combination Fast Analog I/O Module User Manual
Page 24
24 Compact Combination Fast Analog I/O Module
Publication 1769-IN081A-EN-P - February 2007
Certifications
Certification
Value
Agency Certification
•
C-UL certified (under CSA C22.2 No. 142)
•
UL 508 listed
•
CE compliant for all applicable directives
Hazardous Environment Class
Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604,
C-UL under CSA C22.2 No. 213)
Radiated and Conducted Emissions
EN50081-2 Class A
Electrical /EMC:
The module has passed testing at the following levels:
•
ESD Immunity (IEC1000-4-2)
•
4 kV contact, 8 kV air, 4 kV indirect
•
Radiated Immunity (IEC1000-4-3)
•
10 V/m, 80…1000 MHz, 80% amplitude modulation,
+900 MHz keyed carrier
•
Fast Transient Burst (IEC1000-4-4)
•
2 kV, 5 kHz
•
Surge Immunity (IEC1000-4-5)
•
1 kV galvanic gun
•
Conducted Immunity
(IEC1000-4-6)
•
10V dc, 0.15…80 MHz
(1)
(1)
Conducted Immunity frequency range may be 150 kHz…30 MHz if the Radiated Immunity frequency range is 30 MHz…1000
MHz.
Output Specifications
Attribute
Value
Analog Normal Operating Ranges
(1)
(1)
The over- or under-range flag will come on when the normal operating range (over/under) is exceeded. The module will
continue to convert the analog input up to the maximum full scale range. The flag automatically resets when within the
normal operating range unless configured to latch.
0…20 mA, 4…20 mA, +/-10V dc, 0…10V dc, 0…5 V dc, 1…5V dc
Full Scale Analog Ranges
(1)
0…21 mA, 3.2…21 mA, +/-10.5V dc, -0.5…10.5V dc, -0.5… 5.25V
dc, 0.5… 5.25V dc
Number of Outputs
Two single-ended
Digital Resolution Across Full Range
13 bits unipolar, 13 bits plus sign bipolar
Conversion Rate (all channels) max.
1 ms
Step Response to 63%
(2)
(2)
Step response is the period of time between when the D/A converter was instructed to go from minimum to full range until
the device is at 63% of full range.
2.0 ms
Resistive Load
Current: 0…500
Ω
(includes wire resistance)
Voltage: 1 K
Ω
or greater
Max. Inductive Load
0.1 mH (current loads), 1.0 uF (voltage loads)
Field Calibration
None required
Overall Accuracy
(3)
(3)
Includes offset, gain, drift, non-linearity and repeatability error terms.
0.2% full scale at 25 °C