Network (net) status indicator, Network (net) status indicator -5 – Rockwell Automation 1784-PCIDS DeviceNet PCI Communication Interface Card User Manual
Page 57

Interpret Status Indicators (LEDs) 7-5
Publication 1784-IN004E-EN-P - April 2005
Network (NET) Status Indicator
This bi-color (green/red) LED indicates the status of the communication link.
condition
status
indicates
off
not powered,
not online
Device is not online.
The device has not completed the Dup_MAC_ID test yet.
The device may not be powered; look at the Module Status
LED.
flashing green
1
online,
not connected
Device is online, but has no connections in the established
state.
The device has passed the Dup_MAC_ID test, is online, but
has no established connections to other nodes.
green
link okay, online,
connected
The device is online and has connections in the established
state.
flashing red
1
connection time-out
One or more I/O connections are in the timed-out state.
red
critical link failure
Failed communication device. The device has detected an
error that has rendered it incapable of communicating on
the network (Duplicate MAC ID or Bus-off).
Check network integrity and baud rate of all devices. Then
cycle power to the card by shutting down and cycling power
to your computer.
1
The flash rate of the LED is approximately 1 flash per second. The LED should be on for approximately
0.5 seconds and off for approximately 0.5 seconds.