Chapter 4 Change detection
access data using an MSG instruction, refer to t
Use these settings to read the Audit Value attribute using the Message
Configuration.
If you want to Get AuditValue in this
property
Type or select
Message Type
CIP Generic
Service Type
Audit Value Get
Source
Leave blank
Destination
tag_name of type DINT[2] or LINT 1
This tag contains the AuditValue for the controller.
ChangesToDetect Format
Bit number
Event description
0
Project stored to removable media
1
Online edits modified controller program
2
Transaction committed. Indicates that a batch of one or more changes has been applied to the
controller. For example, this might happen when a routine is imported online or when a module
configuration is changed online.
3
SFC forces enabled
4
SFC forces disabled
5
SFC forces removed
6
SFC element force value changed
7
I/O forces enabled
8
I/O forces disabled
9
I/O forces removed
10
I/O forces modified
11
Firmware update attempted
12
Firmware update from removable media attempted
13
Remote mode change
14
Keyswitch mode change
15
A major fault occurred
16
All major faults cleared
17
All major faults cleared through keyswitch
18
Task properties modified
19
Program properties modified
20
Controller time slice modified
21
Removable media removed
50
Rockwell Automation Publication 1756-PM015F-EN-P – October 2014