Rockwell Automation 1791-XXXX Discrete I/O AC and DC Block I/O Input and Output Modules User Manual
Page 41
Installing Block I/O
Chapter 3
3-22
Figure 3.16
Input/Output Wiring Connections for the 1791Ć8BC
Series B
RIO
1
30
PLC and SLC
24V dc
+
Ć
24V dc
+
Ć
24V dc
+
Ć
GND
BLU
CLR
in 00
in 01
in 02
in 03
in 04
in 05
in 06
in 07
RET
in
NOT
USED
SHD
Vdc
out
out 00
out 02
out 03
out 04
out 05
out 06
out 07
Vdc
out
NOT
USED
RET
out
out 01
+24
RET
+24
RET
in
NOT
USED
RET in connections are internally connected together.
Vdc out connections must be externally connected together to accommodate amperage rating.
Output fusing is recommended. Refer to Table 2.B on page 2Ć8.
NOTE:
1
2
29
30
Connections
1791Ć8BC
Series B
Connections
Designation
Description
Terminal No.
Power
+24
+24V dc Power
1
Power
Connections
RET +24
dc Return
3
GND
Chassis ground
2
1
Remote I/O
BLU
Blue wire Ć RIO
6
Remote I/O
Connections
CLR
Clear wire Ć RIO
8
SHD
Shield Ć RIO
7
I/O Connections
Input
in 00 thru in 07
Input 00 thru 07
16, 18, 20, 22, 24, 26, 28, 30
Input
RET in
dc input Return
12, 14
2
Vdc out
dc output Supply
11, 13
3
Output RET out
dc output Return
9
p
out 00 thru out 07
Output 00 thru 07
15, 17, 19, 21, 23, 25, 27, 29
Not used
For internal test only; not
for customer use.
4, 5, 10
1
Connect chassis ground to equipment grounding stud. These are not internally connected.
2
Terminals 12 and 14 are internally connected.
3
Terminals 11 and 13 must be externally connected by customer to accommodate amperage rating.