Calibration setup, Input module – Rockwell Automation 1794-IRT8XT FLEX I/O Thermocouple/RTD /Millivolt Input Module User Manual User Manual

Page 53

background image

Publication 1794-6.5.12 - September 2011

Calibrate Your Module 41

Calibration Setup

Wiring Connections for Calibrating the Thermocouple and RTD Input Module

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

0

Using Precision Resistors -
for 383

Ω

and 100

Ω

calibration

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

16

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

34

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

16

0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

0

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

51

34

1794-TB3G

Precision Voltage Source

Using Precision Voltage Source -
for offset and gain calibration

+

-

Connect + to terminals 2, 6, 10, 14, 19, 23, 27, and 31
Connect - to terminals 3, 7, 11, 15, 20, 24, 28 and 32
Connect one 10 K

Ω

, 0.5% resistor across terminals 37 and 39 and another across 46 and 48.

45357

Type of Input

Connect the following

H

L

+

-

Shield

RTD – 4-wire

1a

2a

1

2

Millivolt

1

2

Wiring to the 1794-TB3G and 1794-TB3GS Terminal Base Units

RTD or
Thermocouple
Channel

1794-TB3G and 1794-TB3GS Terminal Base Units

(1)

High Signal
Terminal (H)

Low Signal
Terminal (L)

RTD Source
Current (+)

Signal Return
(-)

0

1

2

0

3

1

5

6

4

7

2

9

10

8

11

3

13

14

12

15

4

18

19

17

20

5

22

23

21

24

6

26

27

25

28

+

-

mV

1
1a

2

2a

1

2

4-wire

RTD

Millivolt

45358