Rockwell Automation 1794-IRT8XT FLEX I/O Thermocouple/RTD /Millivolt Input Module User Manual User Manual
Page 48
Publication 1794-6.5.12 - September 2011
36
Read and Write Configuration Maps for the FLEX I/O Module
Write Word 1
(continued)
0
0
External compensation
– uses cold junction sensors. Both CJC sensors must be
used when external compensation is selected.
0
1
Internal compensation
– uses the user selected Reference Junction Selection.
1
0
No compensation. Data is referenced to 0 °C (32 °F).
1
1
Differential measurement between 2 channels (0…1, 2…3, 4…5, 6…7)
RTD
0
0
2-wire RTD no compensation
0
1
2-wire RTD with user selected RTD offset
1
0
3-wire RTD
1
1
4-wire RTD
Bits 06…07
Input Type Select
Bit
07 06 Input type selection for channels 0…3
0
0
Thermocouple
0
1
RTD
1
0
Not used
1
1
Not used
Bits 08…11
(10…13)
Sensor Type (Thermocouple or RTD)
RTD Type
Bit
11 10 09 08
Sensor type for channels 4…7
0
0
0
0
Resistance (default)
0
0
0
1
100
Ω
Pt
α
= 0.00385 Euro -200…+870 °C (-328…1598 °F)
0
0
1
0
200
Ω
Pt
α
= 0.00385 Euro -200…+400 °C (-328…752 °F)
0
0
1
1
100
Ω
Pt
α
= 0.003916 U.S. -200…+630 °C (-328…1166 °F)
0
1
0
0
200
Ω
Pt
α
= 0.003916 U.S. -200…+400 °C (-328…752 °F)
0
1
0
1
100
Ω
Nickel -60…+250 °C (-76…482 °F)
0
1
1
0
200
Ω
Nickel -60…+200 °C (-76…362 °F)
0
1
1
1
120
Ω
Nickel -80…+320 °C (-112…608 °F)
1
0
0
0
10
Ω
Copper -200…+260 °C (-328…470 °F)
1001…1111 not used
Bits 08…11
(10…13)
Thermocouple Type
Bit
11 10 09 08
Sensor type for channels 4…7
0
0
0
0
mV (default)
0
0
0
1
B 300…1800 °C (572…3272 °F)
0
0
1
0
E -270…1000 °C (-454…1832 °F)
0
0
1
1
J -210…1200 °C (-346…2192 °F)
0
1
0
0
K -270…1372 °C (-454…2502 °F)
0
1
0
1
TXK/XK(L) -200…800 °C (-328…1472 °F)
0
1
1
0
N -270…1300 °C (-450…2372 °F)
0
1
1
1
R -50…1768 °C (-58…3214 °F)
1
0
0
0
S -50…1768 °C (-58…3214 °F)
Bit/Word Descriptions for Block Transfer Write Words
Word
Dec. Bits
(Octal Bits)
Description