Rockwell Automation 1788-EN2DN Ethernet-to-DeviceNet Linking Device User Manual
Page 52
52 Ethernet-to-DeviceNet Linking Device
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Wire size
DeviceNet connections:
See appropriate system-level installation
manual
Ethernet network connections:
RJ45 connector according to IEC 60603-7, 2
or 4 pair Category 5e minimum cable
according to TIA 568-B.1 or Category 5 cable
according to ISO/IEC 24702
DC Power connections:
0.2… 3.3 mm
2
(24…12 AWG) solid or
stranded copper wire rated at 75 °C (167 °F),
or greater, 1.2 mm (3/64 in.) insulation max
Wiring category
(1)
2 - on power ports
2 - on communication ports
North American temp code
T4
IEC temp code
T4
(1)
Grounding Guidelines, publication
1770-4.1
.
Environmental Specifications - 1788-EN2DN
Attribute
1788-EN2DN
Temperature, operating
• IEC 60068-2-1 (Test Ad, Operating Cold),
• IEC 60068-2-2 (Test Bd, Operating Dry Heat),
• IEC 60068-2-14 (Test Nb, Operating Thermal Shock)
0…60 °C (32…140 °F)
Temperature, surrounding air, max
60 °C (140 °F)
Temperature, nonoperating
• IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating
Cold),
• IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry
Heat),
• IEC 60068-2-14 (Test Na, Unpackaged Nonoperating
Thermal Shock)
-40…85 °C (-40…185 °F)
Technical Specifications - 1788-EN2DN
Attribute
1788-EN2DN