46 Ethernet-to-DeviceNet Linking Device
Rockwell Automation Publication 1788-IN055C-EN-P - September 2011
Node Status
The Node Status page displays the current status of all DeviceNet nodes that are
configured as slaves to the linking device and the linking device itself. The status
of each node is displayed next to the node’s MAC ID. Note that only nodes
configured as slaves to the linking device and the linking device itself are updated
on this page.
The page will display the status textually for many of the common status values.
However, to save web page size, many of the status values are only displayed
numerically. The table below describes the meaning of each status value.
Node Status Codes
This status code
Means
So you should
0
OK
Do nothing.
60
Duplicate MAC ID test in progress
Do nothing.
70
Module failed Duplicate Node Address check
Change the module address to
another available one. The node
address you selected is already in
use on that network.
71
Illegal data in scan list table
Reconfigure the scan list table
and remove any illegal data.
72
Slave device stopped communicating
Inspect the field devices and
verify connections.
73
Device’s identity information does not match
electronic key in scan list table entry
Verify that the correct device is at
this node number. Make sure that
the device at the scrolling node
address matches the desired
electronic key (such as vendor,
product code, and product type).
74
Data overrun on port detected
Modify your configuration and
check for invalid data. Check
network communication traffic.
75
No traffic detected on the network
Check the network configuration.
76
No direct network traffic for module detected
None. The module hears other
network communication.