Connect wiring to the field wiring arm – Rockwell Automation 1771-IR Installation Instructions User Manual

Page 5

background image

Connection Diagram for the RTD Input Module (1771ĆIR/D)

Field Wiring Arm

Cat. No. 1771ĆWF

18

17

16

1

15

14

13

12

11

10

9
8

7

6

5

4

3

2

11846ĆI

RTD

(Channel 1 shown)

Functional

Ground

The sensor cable must be shielded. The shield must:

extend the length of the cable, but be connected only at the 1771 I/O chassis

extend up to the point of termination

Important:

The shield should extend to the termination point, exposing just enough cable to

adequately terminate the inner conductors. Use heat shrink or another suitable

insulation where the wire exits the cable jacket.

RTD Input Module

5

Publication 1771Ć5.63 - November 1998

Connect your I/O devices to the field wiring arm (cat. no. 1771-WF)
shipped with the module.

!

ATTENTION: Remove power from the 1771 I/O
chassis backplane and field wiring arm before
removing or installing an I/O module.

Failure to remove power from the backplane or
wiring arm could cause module damage, degradation
of performance, or injury.

Failure to remove power from the backplane could
cause injury or equipment damage due to possible
unexpected operation.

Channel

Terminal

Identification

1

18

C

17

B

16

A

2

15

C

14

B

13

A

3

12

C

11

B

10

A

4

9

C

8

B

7

A

5

6

C

5

B

4

A

6

3

C

2

B

1

A

Connect Wiring to the

Field Wiring Arm