A-6 Module Specifications
uV Err, ±100mV Span, Prop Cts, 60 Hz, 60°C
Thermocouple
The following table provides the total error expected of the
thermocouple based on the thermocouple type, and the given
reference point, at 25°C. The calculations assumed typical
hardware/software error and typical CJC accuracy at 25°C.
The following table provides the total error expected over the
temperature range of the module (0 to 60°C) for each thermocouple
based upon the type, and the given reference point, at the extremes of
the temperature range (0 or 60°C). The calculations are based on
maximum hardware/software error and maximum CJC inaccuracy
over temperature.
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
-100
-99.92-99.84-99.76-99.68 -99.6-99.52-50.16-50.08 -50 -49.92-49.84 -0.18
-0.1 -0.02 0.06 0.14 49.8 49.8849.96 50.04 50.12 50.2 99.5699.64 99.72 99.8 99.88 99.96
uV Error
mV Input
uV D
e
viatio
n
Thermocouple Type
Thermocouple Reference Point Error
J
+275°C (+527°F)
±1.4°C (±2.52°F)
K
+550°C (+1022°F)
±1.5°C (±2.7°F)
T
+65°C (+149°F)
±1.3°C (±2.34°F)
E
+365°C (+689°F)
±1.3°C (±2.34°F)
R
+885°C (+1625°F)
±3.6°C (±6.48°F)
S
+885°C (+1625°F)
±3.4°C (±6.12°F)
B
+1060°C (+1940°F)
±2.7°C (±4.86°F)
N
+500°C (+932°F)
±1.3°C (±2.34°F)