4-12 Channel Configuration, Data, and Status
Channel Status Checking
You can use the information provided in the status word to determine
if the input configuration data for any channel is valid per your
configuration in O:e.0 through O:e.7.
The channel status can be analyzed bit by bit. In addition to providing
information about an enabled or disabled channel, each bit’s status (0
or 1) tells you how the input data from the thermocouple or millivolt
analog sensor connected to a specific channel will be translated for
your application. The bit status also informs you of any error
condition and can tell you what type of error occurred.
A bit-by-bit examination of the status word is provided in the chart on
the following page.
Channel 0 to 7 Status Word (I:e.0 through I:e.7) - Bit Definitions
To Select
Make these bit settings
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
Channel
Channel Disable
0
Status
Channel Enable
1
Input
Type
Thermocouple J
0
0
0
0
Thermocouple K
0
0
0
1
Thermocouple T
0
0
1
0
Thermocouple E
0
0
1
1
Thermocouple R
0
1
0
0
Thermocouple S
0
1
0
1
Thermocouple B
0
1
1
0
Thermocouple N
0
1
1
1
-50 to +50 mV
1
0
0
0
-100 to +100 mV
1
0
0
1
Invalid
1
0
1
0
Invalid
1
0
1
1
Invalid
1
1
0
0
Invalid
1
1
0
1
Invalid
1
1
1
0
CJC temperature
1
1
1
1
Data
Format
Engineering Units x 1
0
0
Engineering Units x 10
0
1
Scaled-for-PID
1
0
Proportional counts
1
1
Open Circuit
Zero on open circuit
0
0
Max. on open circuit
0
1
Min. on open circuit
1
0
Disabled
1
1
Temperature
units
°C
0
°F
1