Interpreting i/o error codes, Interpreting i/o error codes -5, Channel error (bit 15) – Rockwell Automation 1746-NT8 SLC 500 Thermocouple/mV Analog Input Module User Manual User Manual
Page 77: Module status led (green)

Publication 1746-UM022B-EN-P - January 2005
Troubleshooting Your Module 6-5
Channel Error (Bit 15)
The module sets this fault bit when it detects any of the following
configuration errors:
•
configuration bits 1 through 4: invalid input type = 1010, 1011,
1100, 1101, or 1110.
•
configuration bits 12 through 14: invalid non-zero bit setting.
•
invalid data acquisition of an input channel.
•
the filter frequency selected for the valid channel currently fails
auto-calibration range checks.
Module Status LED (Green)
The module-status LED indicates when the module detects a
non-recoverable fault at power up or during operation. For this type
of fault, the module:
•
no longer communicates with the SLC processor
•
disables all channels
•
clears all data and status words
A module failure is non-recoverable and requires the assistance of
your local Allen-Bradley distributor.
Interpreting I/O Error Codes
I/O error codes appear in word S:6 of the SLC processor status file.
The first two digits of the error code identify the slot (in hexadecimal)
with the error. The last two digits identify the I/O error code (in
hexadecimal).
The error codes that apply to your module include (in hexadecimal):
•
50 through 5E
•
71 (watchdog error)
•
90 through 94
For a description of the error codes, refer to the SLC 500 Instruction
Set Reference Manual, publication 1746-RM001.