4-8 Channel Configuration, Data, and Status
1746-NT8 Thermocouple Module - Channel Data Wo
r
d
Format
1746-NT8 Thermocouple Module - Channel Data Word Resolution
Data Format
Input Type
Engineering Units x10
Engineering Units x1
Scaled for PID Proportional
Counts
°Celsius
°Fahrenheit
°Celsius
°Fahrenheit
J
-210 to +760
-346 to +1400
-2100 to +7600
-3460 to +14000
0 to +16383
-32768 to +32767
K
-270 to +1370
-454 to +2498
-2700 to +13700
-4540 to +24980
0 to +16383
-32768 to +32767
T
-270 to +400
-454 to +752
-2700 to +4000
-4540 to +7520
0 to +16383
-32768 to +32767
E
-270 to +1000
-454 to +1832
-2700 to +10000
-4540 to +18320
0 to +16383
-32768 to +32767
R
0 to +1768
+32 to +3214
0 to +17680
+320 to+32140
0 to +16383
-32768 to +32767
S
0 to +1768
+32 to +2372
0 to +17680
+320 to +32140
0 to +16383
-32768 to +32767
B
+300 to +1820
+572 to +3308
+3000 to +18200
+5720 to +3276.7
(2)
0 to +16383
-32768 to +32767
N
0 to +1300
+32 to +2372
0 to +13000
+320 to +23720
0 to +16383
-32768 to +32767
±50 mV
(1)
-500 to +500
-500 to +500
-5000 to +5000
-5000 to +5000
0 to +16383
-32768 to +32767
±100 mV
(1)
-1000 to +1000
-1000 to +1000
-10000 to +1000
-10000 to +10000
0 to +16383
-32768 to +32767
CJC Sensor
-25 to +105
-13 to +221
-250 to +1050
-130 to +2210
0 to +16383
-32768 to +32767
(1) When millivolts are selected, the temperature setting is ignored. Analog input data is the same for either °C or °F selection.
(2) Type B thermocouple cannot be represented in engineering units x1 (°F) above 3276.7°F. Software treats it as an over range error.
Data Format
Input
Type
Engineering Units x10
Engineering Units x1
Scaled for PID
Proportional Counts
°Celsius
°Fahrenheit °Celsius
°Fahrenheit °Celsius
°Fahrenheit
°Celsius
°Fahrenheit
J
1°C/step
1°F/step
1°C/step
1°F/step
0.0592°C/step
0.1066°F/step 0.0148°C/step 0.0266°F/step
K
1°C/step
1°F/step
1°C/step
1°F/step
0.1001°C/step
0.1802°F/step 0.0250°C/step 0.0450°F/step
T
1°C/step
1°F/step
1°C/step
1°F/step
0.0409°C/step
0.0736°F/step 0.0102°C/step 0.0184°F/step
E
1°C/step
1°F/step
1°C/step
1°F/step
0.0775°C/step
0.1395°F/step 0.0194°C/step 0.0349°F/step
R
1°C/step
1°F/step
1°C/step
1°F/step
0.1079°C/step
0.1942°F/step 0.0270°C/step 0.0486°F/step
S
1°C/step
1°F/step
1°C/step
1°F/step
0.1079°C/step
0.1942°F/step 0.0270°C/step 0.0486°F/step
B
1°C/step
1°F/step
1°C/step
1°F/step
0.0928°C/step
0.1670°F/step 0.0232°C/step 0.0417°F/step
N
1°C/step
1°F/step
1°C/step
1°F/step
0.0793°C/step
0.1428°F/step 0.0198°C/step 0.0357°F/step
±50 mV
(1)
0.1mV/step 0.1mV/step
0.1mV/step
0.1mV/step
6.104µV/step
6.104µV/step
1.526µV/step
1.526µV/step
±100 mV
(1)
0.1mV/step 0.1mV/step
0.1mV/step
0.1mV/step
12.21µV/step
12.21µV/step
3.052µV/step
3.052µV/step
CJC
Sensor
1°C/step
1°F/step
1°C/step
1°F/step
0.0079°C/step
0.0143°F/step 0.0020°C/step 0.0036°F/step
(1) When millivolts are selected, the temperature setting is ignored. Analog input data is the same for either °C or °F selection.