beautypg.com

Module addressing, Channel configuration – Rockwell Automation 1746-NT4 SLC 500 Thermocouple/mV Input Module Installation Instructions User Manual

Page 17

background image

SLC™ 500 4-Channel Thermocouple/mV Input Module 17

Publication 1746-IN010D-EN-P - June 2004

Module Addressing

The following memory map shows you how the output and input image tables are
defined for the thermocouple module.

Channel Configuration

Once the module is installed, each channel on the module can be configured to
establish the way the channel will operate. You configure the channel by entering
bit values into the configuration word using your programming software. Channels
0 through 3 on the NT4 are configured by entering bit values into output words 0
through 3 respectively. Output words 4 through 7 are not used. See the table on
page 18 for bit settings.

SLC 5/0X

Data Files

Slot e

Output Image

Slot e

Input Image

Output

Scan

Input

Scan

Thermocouple
Module Image

Output Image

8 Words

Input Image

8 Words

Output
Image

Input
Image

(Class 1)

Channel 0 Configuration Word

Channel 1 Configuration Word

Channel 2 Configuration Word

Channel 3 Configuration Word

Words 4-7

(not defined)

Channel 0 Data Word

Channel 1 Data Word

Channel 2 Data Word

Channel 3 Data Word

Channel 0 Status Word

Channel 1 Status Word

Channel 2 Status Word

Channel 3 status Word

Address

Bit 15

Bit 0

Address

Bit 15

Bit 0

Word 0

Word 1

Word 2

Word 3

O:e.0

O:e.1

O:e.2

O:e.3

Word 0

Word 1

Word 2

Word 3

Word 4

Word 5

Word 6

Word 7

I:e.0

I:e.1

I:e.2

I:e.3

I:e.4

I:e.5

I:e.6

I:e.7