beautypg.com

Rockwell Automation 1746-NT4 SLC 500 Thermocouple/mV Input Module Installation Instructions User Manual

Page 14

background image

14 SLC™ 500 4-Channel Thermocouple/mV Input Module

Publication 1746-IN010D-EN-P - June 2004

If millivolt inputs are used, the terminal should be biased to a level

within 2V of the signal of interest. Use 10K

Ω resistors to create a resistive

voltage divider as shown in the following circuit diagram.

• Ground the shield drain wire at one end only. The preferred location is to

the same point as the sensor ground reference.

For grounded thermocouples or mV sensors, this is at the sensor.

For insulated/ungrounded thermocouples, this is at the module.

Refer to IEEE Std. 518, Section 6.4.2.7 or contact your sensor

manufacturer for additional details.

• If it is necessary to connect the shield at the module, each input channel has

a convenient shield connection screw terminal that provides a connection to
chassis ground. All shields are internally connected, so any shield terminal
can be used with channels 0-3. For maximum noise reduction, one shield
terminal must be connected to earth ground potential, i.e. mounting bolt on
1746 chassis.

TIP

The Series A 1746-NT4 does not have an ANALOG COM
terminal and cannot be used with multiple grounded and/or
exposed thermocouples that touch electrically conductive
material. The Series A can be used with a single grounded
and/or exposed thermocouple that touches electrically
conductive material, or multiple grounded thermocouples that
have the protective sheath made of an electrically
non-conductive material such as ceramic.

+

-

+

Strain Gauge
Bridge

NT4

Vcc

10K

10K

variable

fixed

fixed

fixed

Input

(CHL 0, CHL 1, CHL
2, CHL 3)

Analog Com