Module Configuration

Chapter 5

5Ć8

Word

Description

Bits

Words 20

thru 27

Calibration words are a composite of two independent bytes for each

channel. Enter calibration data in signed magnitude binary only. The

most significant bit in each byte is the sign bit; set for negative, reset

for positive.

Use the high byte (bits 08-15) for offset correction, the low byte (bits

00-07) for gain correction for each channel. Use word 20 for channel

1 thru word 27 for channel 8.

Refer to Chapter 7 for calibration procedures.

Word 28

Auto-calibration request word - used to automatically calibrate

selected channels and save the calibration constants in EEPROM.

(Refer to Chapter 7.)

Table 5.E

Example Zoom Settings for Word 2

Zoom Settings

Bit Settings (15-08) or (07-00)

Zoom center = 70mV (maximum)

01000110 (decimal equivalent 70)

Zoom center = 0mV

00000000 (decimal equivalent 0)

Zoom center = -1mV

11111111 (decimal equivalent -1)

Zoom center = -70mV (minimum)

10111010 (decimal equivalent -70)

Only used in millivolt mode with Z = 1. Millivolt data will be in 1

µ

V resolution with range of +30.000mV.

Zoom will be used to center the range of interest between +70mV. Over and underrange bits will be

asserted outside of the display range. For decimal equivalent values from 71 to 127 and -71 to -128

the zoom center will default to 0.

Table 5.F

Example Filter Values for Word 3

Filter Value

Bit Setting

(15-08) or (07-00)

No filter

0000000

Tau = 50ms

00000001

Tau = 75ms

00000010

Tau = 6.4 seconds

11111111

Filter values increase in increments of 25msec.

In this chapter you learned how to configure your module’s hardware, condition
your inputs and enter your data.

Chapter Summary