Publication 1762-UM002A-EN-P - July 2002
Module Data, Status, and Channel Configuration 3-35
separate ADC self-calibration and offset calibration cycles only if their
filter configurations are different than those of previously calibrated
channels.
Following all input channel calibration cycles, the CJC sensor channel
receives a separate ADC self-calibration cycle. The time added to this
cycle is determined by the filter setting for the CJC, which is set to the
lowest filter setting of any input configured as a thermocouple. If no
enabled input channel is configured for a thermocouple, no CJC
calibration cycle occurs. See Table 3.6 below for channel and CJC
sensor ADC self-calibration times as well as channel offset calibration
times.
Calculating Module Update Time
To determine the module update time, add the individual channel
update times for each enabled channel and the CJC update time if any
of the channels are enabled as thermocouple inputs.
Table 3.6 Calibration Time
Type of Calibration
10 Hz
50 Hz
60 Hz
250 Hz
500 Hz
1 kHz
ADC self-calibration
(Channels 0 through 3)
603
123
103
27
15
9
Offset calibration
(Channels 0 through 3)
303
63
53
15
9
6
ADC self-calibration
(CJC sensor)
603
123
103
27
15
9
EXAMPLE
1. Two Channels Enabled for Millivolt Inputs
Channel 0 Input: ±50 mV with 60 Hz filter
Channel 1 Input: ±50 mV with 500 Hz filter
From Table 3.5, Channel Update Time, on page 3-34:
Module Update Time
= Ch 0 Update Time + Ch 1 Update Time
= 53 ms + 9 ms
= 62 ms