Rockwell Automation 1762-IT4 Thermocouple/mV Input Module User Manual

Page 128

background image

Publication 1762-UM002A-EN-P - July 2002

E-2 Module Configuration Using MicroLogix 1200 and RSLogix 500

1762-IT4 Configuration File

The configuration file contains information you use to define the way
a specific channel functions. The configuration file is explained in
more detail in Configuring Channels on page 3-4.

The configuration file is modified using the programming software
configuration screen. For an example of module configuration using
RSLogix 500, see Configuration Using RSLogix 500 Version 5.50 or
Higher on page E-2
.

Configuration Using
RSLogix 500 Version 5.50 or
Higher

This example takes you through configuring your 1762-IT4
thermocouple/mV input module with RSLogix 500 programming
software, assumes your module is installed as expansion I/O in a
MicroLogix 1200 system, and that RSLinx™ is properly configured and
a communications link has been established between the MicroLogix
processor and RSLogix 500.

Table 5.1 Software Configuration Channel Defaults

Parameter

Default Setting

Disable/Enable Channel

Disable

Filter Frequency

60 Hz

Input Type

Thermocouple Type J

Data Format

Raw/Proportional

Temperature Units

°C

Open-Circuit Response

Upscale

Disable Cyclic Calibration

Enable