Appendix b – technical data, 825 plus, Conversion kit interface panel – Rockwell Automation 1500 Modular Protection System Conversion Kit (Bulletin 1406 to Bulletin 825 Plus) User Manual
Page 27: Technical data, Appendix

Appendix
B
1500-IN058D-EN-E – June 2013
Technical Data
825 Plus
Refer to Publication 825-UM004_-EN-P.
Conversion Kit Interface Panel
Description
Specification
Ground Fault Interposing Current Transformer
Primary 1A
Secondary 5A
Operating Frequency
50/60 Hz
Class 600
V
Accuracy
Less than 2% ratio error at 5 VA burden
Primary Impedance
2.5 ohms
Approvals
CSA certified and UL listed
Important:
This current transformer is used to step down an existing 50:5 ground fault current transformer.
The secondary of this current transformer is connected to the secondary of the existing ground
fault current transformer. This results in an equivalent 50:1 ground fault current transformer.
This is done to prevent possible damaging current levels for the 825 Plus.
Voltage Transformer (not provided with the standard kits)
(Optional for speed switch appliclations)
Primary
115 V AC
Secondary
24 V AC @ 60 Hz
Current Rating
85 mA
Class Insulation
105°C
Di-electric Withstand
Hi-Pot test of 2000 V RMS
Approvals
CSA certified and UL listed
Design Type
Dual bobbin design – no electrostatic shield required
Recommended Transformer
M
anufacturer:
Hammond Manufacturing
P
art Number:
166C24
Auxiliary Relays
(Bulletin 700-HK32A1)
Temperature
Operating: -30°C to +55°C (-22°F to +131°F)
Storage:
-55°C to +85°C (-67°F to +185°F)
Enclosure
Transparent Dust Cover
Coil
Voltage
120 V AC @ 60 Hz
Permissible Coil Voltage Variation
102 V AC to 132 V AC
Power Consumption
± 10% AC – 1.1 VA
Rated Insulation Voltage
250 V IEC; 300 V UL/CSA
Dielectric Withstand Voltage
Pole to Pole (VRMS):
1500 V AC
Contact to Coil (VRMS): 1500 V AC
Contacts
Type
DPDT, 2 Pole, 2 Form C
Material S
ilver Cadmium Oxide (AgCdO)
Mechanical Operations
5 x 10
6
Switching Frequency Operations
11,800/hr
Rated Thermal Current
5 A
Break Current at 120 V AC
3 A
Make Current at 120 V AC
30 A
Operating Time
P
ickup:
15 ms
Dropout
:
15 ms
Maximum Operating Rate
3 Ops/s