Rockwell Automation 1395 Node Adapter Board User Manual
Page 64

Chapter 6
Troubleshooting and Maintenance
6-2
Certain fault conditions in the Bulletin 1395 can be configured in terms of
their Soft or Warning Fault nature. That is, the user/operator may specify
the action taken, either Soft Fault or Warning Fault (Report Only).
ATTENTION: Ignoring faults that have been configured as
Report Only could damage certain components in the drive.
Examples of Soft/Warning Faults configurable by users are:
S Motor Overtemperature
S AC Line Out of Tolerance
S Heat Sink Overtemperature
Node Adapter Fault Messages
The fault messages available on the Discrete Adapter Board are:
S NA-01 – NODE ADAPTER – PROCESSOR OK
Default state, no error exists.
S NA-02 through NA-05 – NOT USED
Reserved for future use.
S NA-06 – HANDSHAKE TIMEOUT
Communication malfunction between Node Adapter Board and Main
Control Board. Replace Adapter Board, replace Main Control Board.
S NA-07 – NOT USED
Reserved for future use.
S NA-08 – NO COMSOF
Communication malfunction between Node Adapter Board and PLC
Controller. Check wiring, PLC Controller, replace Adapter Board.
S NA-09 – ILLEGAL MODE SEQUENCE
Incorrect mode detected. Replace Main Control Board, replace Node
Adapter Board.
S NA-10 – NO INPUT IMAGE
Communication malfunction between Node Adapter Board and PLC
Controller. Check wiring, PLC Controller, replace Adapter Board.
S NA-11 – OUTPUT IMAGE LOST
Communication malfunction between Node Adapter Board and PLC
Controller. Check wiring, PLC Controller, replace Adapter Board.
S NA-12 – SIU BUFFER OVERFLOW
Communication malfunction between Node Adapter Board and PLC
Controller. Check wiring, PLC Controller, replace Adapter Board.
S NA-13 – PLC COMMAND ILLEGAL
Communication malfunction between Node Adapter Board and PLC
Controller. Check wiring, PLC Controller, replace Adapter Board.