beautypg.com

Rockwell Automation 1395 Node Adapter Board User Manual

Page 56

background image

Chapter 4
Installation

4-6

Table 4.A
Rack Address Switch Settings (U5)

Rack#

SW 1

SW 2

SW 3

SW 4

SW 5

SW 6

00

ON

ON

ON

ON

ON

ON

01

ON

ON

ON

ON

ON

X

02

ON

ON

ON

ON

X

ON

03

ON

ON

ON

ON

X

X

04

ON

ON

ON

X

ON

ON

05

ON

ON

ON

X

ON

X

06

ON

ON

ON

X

X

ON

07

ON

ON

ON

X

X

X

10

ON

ON

X

ON

ON

ON

11

ON

ON

X

ON

ON

X

12

ON

ON

X

ON

X

ON

13

ON

ON

X

ON

X

X

14

ON

ON

X

X

ON

ON

15

ON

ON

X

X

ON

X

16

ON

ON

X

X

X

ON

17

ON

ON

X

X

X

X

20

ON

X

ON

ON

ON

ON

21

ON

X

ON

ON

ON

X

22

ON

X

ON

ON

X

ON

23

ON

X

ON

ON

X

X

24

ON

X

ON

X

ON

ON

25

ON

X

ON

X

ON

X

26

ON

X

ON

X

X

ON

27

ON

X

ON

X

X

X

30

ON

X

X

ON

ON

ON

31

ON

X

X

ON

ON

X

32

ON

X

X

ON

X

ON

33

ON

X

X

ON

X

X

34

ON

X

X

X

ON

ON

35

ON

X

X

X

ON

X

36

ON

X

X

X

X

ON

37

ON

X

X

X

X

X

(1) IMPORTANT: When using the PLC 5/15 or 5/25, the following series and software revisions
are required as a minimum.

Series

Revision

PLC 5/15

B

J

PLC 5/25

A

E

X = OFF or Open