INSTRUCTION SHEET

BULLETIN 1102C VACUUM CONTACTOR

CURRENT RATINGS 200A

200V-1500V

2-20-04

Mark Jutz

2-20-04

D. Josef

2-20-04

3

9

REVISION

AUTHORIZATION

DIMENSIONS APPLY BEFORE

SURFACE TREATMENT

H

A

B

C

D

E

F

G

(DIMENSIONS IN INCHES)

TOLERANCES UNLESS

OTHERWISE SPECIFIED

REFERENCE

SHEET

OF

DWG.

B

DR.

CHKD.

APPD.

DATE

DATE

DATE

±

±
±

ANGLES:

.XXX:

.XX:

THIS DRAWING IS THE PROPERTY OF

THE ALLEN-BRADLEY CO. INC.

AND MAY NOT BE COPIED, USED OR

DISCLOSED FOR ANY PURPOSE EXCEPT

AS AUTHORIZED IN WRITING BY

THE ALLEN-BRADLEY CO. INC.

LOCATION : MILWAUKEE,

WISCONSIN

U.S.A.

SIZE

1

2

3

4

5

6

7

8

E - DOC

Coil Replacement Instructions (Cont'd)

6. Remove and replace the coil. Ensure that the Shim Plate remains in the proper position between the magnet core and coil (Figure 3C).
7.
Carefully replace the Upper Housing, ensuring that it is orientated correctly and that the Return Springs are seated on the outer two
bumps on the bottom of the Contact Operator

(Figure 3D). Replace the (6) screws that secure the Upper Housing. Tighten the screws

equally in a diagonal pattern approximately two turns at a time until tightened to 12 lb-inches in the same diagonal pattern

(Figure 3A).

8. Reinstall the Control-Pak (Figures 3E & 3F). First, insert the lower tab into the recess on the side of the contactor base. With proper
installation, the Control-Pak Actuator will fit into the hole in the slot in the side of the contactor housing. Using a thin rod or flat blade, lift the
Control-Pak Actuator up as necessary to insert it into the slot mentioned

.

9. Reinstall the cover with Retainer and secure it with the original mounting hardware. Tighten the four screws in a diagonal pattern to 5 lb-
inches

(Figure 3A).

10. Reattach the coil wire leads to the Control-Pak (tighten to 7 lb-inches).
11. Reinstall the device and reconnect any auxiliary control wires. Reconnect the line and load conductors and tighten the main terminal
hardware and bolts to 132 lb-inches.

Figure 3D

Figure 3E

Figure 3F

(3)

Figure 3C

Coil

Shim

Plate

Control-Pak

Actuator

Bumps

Control-Pak
Actuator

Actuator
must fit into slot
shown

Thin rod or flat blade