All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

6

Rockwell Automation Publication 1606-RM043A-EN-P — March 2014

Bulletin 1606 Switched Mode Power Supplies

6. Output

Output voltage

nom.

48V

Adjustment range

min.

48-56V

guaranteed

max.

60V

****)

at clockwise end position of potentiometer

Factory settings

typ.

48.0V

±0.2%, at full load, cold unit, in “single use” mode

typ.

46.0V

±0.2%, at full load, cold unit, in “parallel use” mode

typ.

48.0V

at no load, cold unit, in “parallel use” mode

Line regulation

max.

10mV

85-300Vac

Load regulation

max.

150mV

in “single use” mode: static value, 0A 10A;
see Fig. 6-1

typ.

2000mV

in “parallel use” mode: static value, 0A 10A,
see Fig. 6-2

Ripple and noise voltage

max.

50mVpp

20Hz to 20MHz, 50Ohm

Output current

nom.

10A

at 48V, ambient temperature <60°C, see Fig. 6-1

nom.

12A

*)

at 48V, ambient temperature <45°C, see Fig. 6-1

nom.

8.6A

at 56V, ambient temperature <60°C, see Fig. 6-1

nom.

10.3A

*)

at 56V, ambient temperature <45°C, see Fig. 6-1

typ.

40A

up to 15ms,output voltage stays above 40V, see Fig.
6-4. This peak current is available once every five
seconds. See section 22.1 for more peak current
measurements.

Output power

nom.

480W

continuously available

nom.

576W

*)

Power

Boost

*)

Overload behaviour

cont. current

output voltage >25Vdc, see Fig. 6-1

Hiccup

PLUS

mode

**)

output voltage <25Vdc, see Fig. 6-1

Short-circuit current

min.

18A

***)

load

impedance

<10mOhm,

see

Fig.

6-3

max.

22A

***)

load

impedance

<10mOhm,

see

Fig.

6-3

max. 7A

***)

average

(R.M.S.)

current,

load

impedance

100mOhm,

see Fig. 6-3

min.

40A

up to15ms, load impedance <10mOhm, see Fig. 6-4

typ.

50A

up to15ms, load impedance <10mOhm, see Fig. 6-4

Output capacitance

typ.

2 450μF

included inside the power supply

*)

Power Boost

This power/ current is continuously allowed up to an ambient temperature of 45°C. Above 45°C, do not use this power/ current longer
than a duty cycle of 10% and/ or not longer than 1 minute every 10 minutes.

**)

Hiccup

PLUS

Mode

At heavy overloads (when output voltage falls below 25V), the power supply delivers continuous output current for 2s. After this, the
output is switched off for approx. 18s before a new start attempt is automatically performed. This cycle is repeated as long as the
overload exists. If the overload has been cleared, the device will operate normally. See Fig. 6-3.

***) Discharge

current

of

output capacitors is not included.

****) This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. There is no

guarantee that this value can be achieved. The typical value is about 57.0V (in “single use” mode).