Ac-input – Rockwell Automation 1606-XLE480FP Power Supply Reference Manual User Manual
Page 4
All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
4
Rockwell Automation Publication 1606-RM043A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
3. AC-Input
AC input
nom.
AC 100-240V
suitable for TN-, TT- and IT mains networks
AC input range
min.
100-264Vac
continuous operation
min.
85-100Vac
short term or with output derating (1%/V) or with
reduced ambient temperature, see Fig. 15-1,
no damage between 0 and 100Vac
min.
264-300Vac
<
500ms
Allowed voltage L or N to earth
max.
300Vac
continuous, IEC 62103
Input frequency
nom.
50–60Hz
±6%
Turn-on voltage
typ.
84Vac
steady-state value, see Fig. 3-1
Shut-down voltage
typ.
39Vac
steady-state value at 2.5A load, see Fig. 3-1
typ.
53Vac
steady-state value at 5A load, see Fig. 3-1
typ.
74Vac
steady-state value at 10A load, see Fig. 3-1
AC 100V
AC 120V
AC 230V
Input current
typ.
5.25A
4.36A
2.33A
at 48V, 10A, see Fig. 3-3
Power factor
*)
typ.
0.99
0.99
0.95
at 48V, 10A, see Fig. 3-4
Crest factor
**)
typ.
1.5
1.5
1.65
at
48V,
10A
Start-up delay
typ.
850ms
850ms
650ms
see Fig. 3-2
Rise time
typ.
90ms
90ms
90ms
at 48V, 10A const. current load,
0mF load capacitance, see Fig. 3-2
typ.
230ms
230ms
230ms
at 48V, 10A const. current load,
10mF load capacitance, see Fig. 3-2
Turn-on overshoot
max.
200mV
200mV
200mV
see Fig. 3-2
*)
The power factor is the ratio of the true (or real) power to the apparent power in an AC circuit.
**) The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform.
Fig. 3-1 Input voltage range
Fig. 3-2 Turn-on behavior, definitions
Turn-on
85V
Rated
input range
max.
500ms
V
IN
P
OUT
300Vac
264V
Shut
-down
Start-up
delay
Rise
Time
Ov
ersh
oot
- 5%
Output
Voltage
Input
Voltage
Fig. 3-3 Input current vs. output load at 48V
Fig. 3-4 Power factor vs. output load
12A
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6A
Input Current, typ.
10 11
230V
ac
120
Vac
100
Va
c
Output Current
Power Factor, typ.
1
2
3
4
5
6
7
8
9
12A
0.75
0.8
0.85
0.9
0.95
1.0
230Vac
100Vac, 120Vac
10 11
Output Current