All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM043A-EN-P — March 2014

15

Bulletin 1606 Switched Mode Power Supplies

16. Protection Features

Output protection

Electronically protected against overload, no-load and short-circuits

*)

Output over-voltage protection

typ. 58.5Vdc
max. 60Vdc

In case of an internal power supply defect, a redundant
circuit limits the maximum output voltage. The output
shuts down and automatically attempts to restart.

Degree of protection

IP 20

EN/IEC 60529
Caution: For use in a controlled environment according
to CSA 22.2 No 107.1-01.

Penetration protection

> 5mm

e.g. screws, small parts

Over-temperature protection

yes

Output shut-down with automatic restart

Input transient protection

MOV (Metal Oxide Varistor)

Internal input fuse

included

not user replaceable

*) In case of a protection event, audible noise may occur.


17. Safety Features

Input / output separation

*)

SELV

IEC/EN

60950-1

PELV

IEC/EN 60204-1, EN 50178, IEC 62103, IEC 60364-4-41

double or reinforced insulation

Class of protection

I

PE (Protective Earth) connection required

Isolation resistance

> 5MOhm

input to output, 500Vdc

PE resistance

< 0.1Ohm

Touch current (leakage current)

typ. 0.14mA / 0.37mA

100Vac, 50Hz, TN-,TT-mains / IT-mains

typ. 0.20mA / 0.55mA

120Vac, 60Hz, TN-,TT-mains / IT-mains

typ. 0.35mA / 0.87mA

230Vac, 50Hz, TN-,TT-mains / IT-mains

max. 0.17mA / 0.46mA

110Vac, 50Hz, TN-,TT-mains / IT-mains

max. 0.26mA / 0.67mA

132Vac, 60Hz, TN-,TT-mains / IT-mains

max. 0.46mA / 1.08mA

264Vac, 50Hz, TN-,TT-mains / IT-mains

*) double or reinforced insulation