External input protection, Output circuit breakers – Rockwell Automation 1606-XLE480FP Power Supply Reference Manual User Manual
Page 20
All parameters are specified at 48V, 10A, 230Vac, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.
20
Rockwell Automation Publication 1606-RM043A-EN-P — March 2014
Bulletin 1606 Switched Mode Power Supplies
22.3. External Input Protection
The unit is tested and approved for branch circuits up to 30A (UL) and 32A (IEC). An external protection is only
required if the supplying branch has an ampacity greater than this. Check also local codes and local requirements. In
some countries local regulations might apply.
If an external fuse is necessary or utilized, minimum requirements need to be considered to avoid nuisance tripping of
the circuit breaker. A minimum value of 10A B- or C-Characteristic breaker should be used.
22.4. Output Circuit Breakers
Standard miniature circuit breakers (MCBs or UL1077 circuit breakers) are commonly used for AC supply systems and
may also be used on 48V branches.
MCBs are designed to protect wires and circuits. If the ampere value and the characteristics of the MCB are adapted to
the wire size that is used, the wiring is considered as thermally safe wether the MCB opens or not.
To avoid voltage dips and under-voltage situations in adjacent 48V branches which are supplied by the same source, a
fast (magnetic) tripping of the MCB is desired. A quick shutdown within 10ms is necessary corresponding roughly to
the ride-through time of PLCs. This requires power supplies with high current reserves and large output capacitors.
Furthermore, the impedance of the faulty branch must be sufficiently small in order for the current to actually flow.
The best current reserve in the power supply does not help if Ohm’s law does not permit current flow. The following
table has typical test results showing which B- and C-Characteristic MCBs magnetically trip depending on the wire cross
section and wire length.
Fig. 22-3 Test circuit
Maximal wire length
*)
for a fast (magnetic) tripping:
0.75mm² 1.0mm² 1.5mm² 2.5mm²
C-2A
74m 98m 134m
198m
C-3A
57m 74m 106m
168m
C-4A
43m 56m 73m 114m
C-6A
11m 16m 23m 33m
C-8A
1m 1m 2m 3m
B-6A
19m 36m 51m 82m
B-10A
9m 12m 18m 27m
MCB
Power Supply
AC
DC
+
-
+
-
Load
Wire length
S1... Fault simulation switch
S1
B-13A
7m 10m 16m 24m
*)
Don’t forget to consider twice the distance to the load (or cable length) when calculating the total wire length (+ and – wire).