Rockwell Automation 1608 HC-DySC User Manual, 200 A User Manual
Rockwell Automation Equipment
Table of contents
Document Outline
- Important User Information
- Additional Resources
- Chapter 1
- Chapter 2
- Chapter 3
- Chapter 4
- Applying Power and Operation
- Applying Power
- HC-DySC System Operation
- System Description
- Maintenance Bypass Operation
- Bypass Switch Modes
- Maintenance Bypass Transfer Procedure
- Manual transfer to Bypass (maintenance) mode:
- Manual transfer to Normal (sag protection) mode:
- 1. Rotate CBI handle to the off/reset position then to the on position. Note: HC-DySC prevents re-closure of CBI within 1 minute of opening.
- 2. Rotate the bypass switch to the Test position. ATTENTION: The bypass contacts are all timed to make-before-break and will not disrupt power to the load during any mode transitions. The switch has lockout/tagout (LOTO) provisions. Delay one second ...
- 3. Verify the screen on the HC-DySC displays “OK” in the upper left-hand corner of the home page.
- 4. Rotate the bypass switch to the Normal position.
- 5. The HC-DySC system is now providing power to the load.
- Operating and Alarm Modes
- Applying Power and Operation
- Chapter 5
- Chapter 6
- Maintenance
- Preventative Maintenance
- Monthly Checks
- 3-6 Month Checks
- POWER_ON
- Informational
- Unit
- T_FAN_ST
- Informational
- Unit
- T_IN_ST_1
- Informational
- Unit
- T_IN_ST_2
- Informational
- Unit
- T_IN_ST_3
- Informational
- Unit
- EXTERNAL
- Auto-Resetting
- Inverter
- RUN_TO
- Auto-Resetting
- Inverter
- LIM_CYCLE
- Auto-Resetting
- Inverter
- STAT_OT
- User Attention
- Static Switch
- OVERLOAD
- User Attention
- Unit
- DC_OV
- User Attention
- Inverter
- CNTRL_UV
- User Attention
- Inverter
- OUTPUT_UV
- User Attention
- Inverter
- INV_OC
- User Attention
- Inverter
- DC_UV
- User Attention
- Inverter
- OUTPUT_OV
- Call Service
- Inverter
- SYNC_ERR
- Call Service
- Inverter
- CONFIG
- Call Service
- Inverter
- CNTRL_MEM
- Auto-Resetting
- Inverter
- UNBALANCE
- Call Service
- Inverter
- AC_V_CHK
- Call Service
- Inverter
- ROLL_CALL
- Call Service
- Unit
- COM_VER
- Call Service
- Unit
- CNFG_TO
- Call Service
- Unit
- CNFG_ERR
- Call Service
- Unit
- FIRM_TO
- Call Service
- Unit
- FIRM_DIFF
- Call Service
- Unit
- SRL_TO
- Call Service
- Unit
- SRL_DIFF
- Informational
- Unit
- T_INV_TO
- Call Service
- Unit
- Servicing
- Preventative Maintenance
- Maintenance
- Chapter 7