Com_ver, Call service, Unit – Rockwell Automation 1608 HC-DySC User Manual, 200 A User Manual
Page 33: Cnfg_to, Cnfg_err, Firm_to, Firm_diff, Srl_to, Srl_diff, Informational
33
Rockwell Automation Publication 1608P-UM004A-EN-P - September 2013
Chapter 6
Maintenance
36
COM_VER
Start-Up Test: Communication
Compatibility Mismatch
Call Service
Unit
Firmware communication compatibility problem detected during start-up
test.
Call service.
37
CNFG_TO
Start-Up Test: Controller Configuration
Timeout
Call Service
Unit
Controller communication problem detected during start-up test.
Call service.
38
CNFG_ERR
Start-Up Test: Controller Configuration
Mismatch
Call Service
Unit
Controller firmware configuration problem detected during start-up test.
Call service.
39
FIRM_TO
Start-Up Test: Controller Firmware
Check Timeout
Call Service
Unit
Controller communication problem detected during start-up test.
Call service.
40
FIRM_DIFF
Start-Up Test: Controller Firmware
Revision Mismatch
Call Service
Unit
Controller firmware revision mismatch detected during start-up test.
Call service.
41
SRL_TO
Start-Up Test: Controller Serial Number
Check Timeout
Call Service
Unit
Controller communication problem detected during start-up test.
Call service.
42
SRL_DIFF
Start-Up Test: Serial Number Mismatch
Informational
Unit
Controller serial number mismatch detected during start-up test.
No action needed.
44
T_INV_TO
Inverter Test Timeout
Call Service
Unit
Phase control board failed to respond to Comm board's Inverter test.
Call service.
46
DOOR_OPEN
DySC Cabinet Door Open
Manual Reset
Unit
DySC door was opened. Mechanical bypass commanded.
Close door. Manually reset DySC.
47
CRIT_OT
Critical Over-Temperature
Manual Reset
Unit
Internal DySC temperature exceeded maximum rating. Mechanical bypass
commanded.
Verify ambient temperature is within DySC specification.
Check for damaged fans. Check for dirty or obstructed air filters.
Manually reset DySC.
48
FUSE_OPEN
Fuse Open
Call Service
Unit
One of the DySC fuses was detected open. Mechanical bypass commanded.
Call service.
49
OPEN_SCR_A
Open SCR Phase A
Call Service
Static Switch
The SCR on the phase A module was detected open.
Call service.
50
OPEN_SCR_B
Open SCR Phase B
Call Service
Static Switch
The SCR on the phase B module was detected open.
Call service.
51
OPEN_SCR_C
Open SCR Phase C
Call Service
Static Switch
The SCR on the phase C module was detected open.
Call service.
53
DYN_BRAKE
Dynamic Brake Error
Call Service
Unit
A problem was detected with the DySC dynamic brake controller.
Call service.
58
PLC_ERR
Programmable Logic Controller Error
Call Service
PLC
PLC error detected.
Call service.
59
PLC_ST_MM
Programmable Logic Controller State
Mismatch
Call Service
Unit
PLC feedback error detected.
Call service.
Event
Code
Code Name
Full Name
Severity
Area
Event Description
Event Resolution