beautypg.com

Hc-dysc system operation, System description, Figure 8 - one line diagram of the hc-dysc system – Rockwell Automation 1608 HC-DySC User Manual, 200 A User Manual

Page 16: Maintenance bypass operation, Hc-dysc system operation system description

background image

16

Rockwell Automation Publication 1608P-UM004A-EN-P - September 2013

Chapter 4

Applying Power and Operation

HC-DySC System Operation

System Description

The HC-DySC system consists of the DySC dynamic voltage sag correction
electronics together with an integral maintenance bypass switch. In the Normal
mode of operation the raw utility power is routed through the DySC electronics
to protect the loads from voltage sags and momentary interruptions.

Figure 8

shows a simplified one-line diagram for the system. Neutral and Ground
connections are passed straight through to the loads.

Figure 8 - One Line Diagram of the HC-DySC System

Maintenance Bypass
Operation

The HC-DySC has an integral maintenance bypass switch. The maintenance
bypass switch is used to avoid power interruptions to the critical loads during
maintenance or service. The bypass is a 3 position make-before-break rotary
switch.

SHOCK HAZARD: Dangerous voltages are present within the HC-DySC System.
The unit should never be operated with the enclosure door open except by
qualified and authorized personnel who are trained and familiar with the
operation of the unit and the location of components and voltages. Failure to
comply with this warning could result in injury or death.

L1, L2, L3

X1, X2, X3

DySC

ELECTRONICS

OUTPUT TO

PROTECTED LOADS

CBI CIRCUIT

BREAKER

OUTPUT

CONTACTS

INPUT

CONTACTS

BYPASS CONTACTS

UTILITY INPUT

CBA CIRCUIT

BREAKER