Chapter 2

Installation

Floor Mounting

The HC-DySC is to be secured to the floor using fasteners and fittings
appropriate for the type of floor. Holes are provided in the base channels; see

Figure 1

for mounting dimensions.

Note: Top or bottom cable entry is allowed. See

Figure 1

and

Figure 2 on page 9

.

Figure 1 - Bottom View Floor Mount Dimensions

Clearance

HC-DySC doors hinge on both right and left. See

Figure 30 on page 38

for

dimensions including door swing. Leave required clearances:

Door swing must allow doors to open at least 90 degrees

12” [300mm] clearance on left side and rear for cooling airflow

4”[100mm] on right side for air filter clearance when right door opens

Circuit Breaker
Recommendations

Branch circuit protection upstream of the HC-DySC is required. Recommended
circuit breakers and maximum allowed circuit breaker ratings are listed in

Table 1

. Branch circuit protection rated less than the HC-DySC current rating

may result in nuisance tripping.

Table 1 - Recommended Branch Circuit Protection

Electrical Terminations

The HC-DySC must be installed by a qualified electrician, in compliance with
all local and national electric codes. The HC-DySC input (line) and output
(load) terminals are located behind the right door. Terminal details are shown in

Figure 5 on page 12

.

HC-DySC Rating

Max. MCCB Rating

200 A

250 A