Rockwell Automation Publication 1608M-UM003A-EN-P - December 2013

41

Display Screen

Chapter 6

System Event Detail

The “System Event Detail” screen is displayed when a specific system event is
selected by pressing on the “SELECT” button on the “SYSTEM EVENT LOG”
screen (See

Figure 30 on page 40

). It provides detailed information that was

recorded during the event (See

Figure 31

).

Figure 31 - System Event Detail

Table 8 - System Event Detail

Description

Function

Time/Duration

Time: Date and start time of the system event
Duration: The amount of time the event lasted.

Type

Event ID: Unique ID within the list (0-39) to identify the event.
Code: Abbreviation of the event followed by a numeric event code in parentheses. (For a
list of codes and abbreviations see

Table 10 on page 46

Severity: Severity of the event
Description: Name of the event see

Table 10 on page 46

Component

Location: The location in the system where the event originated (i.e. Phase A, Phase B,
Phase C, etc.).
Area: The specific area within the location where the event originated (i.e. Inverter, etc.).
Reading: a data value relevant to the System Event may be recorded in some cases, e.g.,
detail for an “Inverter Over-Current” alarm would include a reading of the causal high
current value. The reading “N.A.” is displayed if no appropriate data value exists.