Table 1 - operational conditions and indications, Automatic bypass switchboard operation – Rockwell Automation 1608M MegaDySC User Manual, 800 Amp - 208V User Manual
Page 26
26
Rockwell Automation Publication 1608M-UM003A-EN-P - December 2013
Chapter 5
Operation
whenever the MegaDySC system is in the maintenance bypass mode (CBB
closed and CBI open).
A list of conditions and indications is given in
. Refer to
for
further information on system alarms and status display.
Table 1 - Operational Conditions and Indications
* The touchscreen will power down if both input and output voltages fall below approx. 75% of nominal
**An error message will be displayed while the red or orange text box is displayed. Refer to
for further information on accessing
fault codes and status history.
Automatic Bypass
Switchboard Operation
The Automatic Bypass Switchboard consists of a bypass circuit breaker (CBB),
an input circuit breaker (CBI), and an output circuit breaker (CBO). Under
normal operating conditions raw input power is routed through CBI to the input
of the MegaDySC. The output of the MegaDySC is routed to the load through
CBO. CBB is normally open. CBB connects utility power to the load, bypassing
the MegaDySC, when operating in the maintenance bypass mode.
for descriptions of the automatic bypass modes
CONDITION
DEFINITION
Touchscreen Display STATUS text*
INVERTER OPERATION BYPASS MODE
Normal:
88.5% < V
LINE
< 110%
Green “OK”
Standby
Static BP
Sag Event:
V
LINE
< 88.5% for less than available
runtime.
Green “OK”
Running
Inverter
Runtime Exceeded:
Cumulative runtime exceeded
Blinks Red, then Orange for 1 min. Repeats
is condition persists
Inhibited
Static BP
Normal Mode, Overload:
Load current > 110%
Red during OL condition,
Orange for 1 min. after OL ends
Inhibited
Static BP
Inverter Run Mode, Output
Overcurrent: (I
2
t)
Load current > 150% for 3 cycles
Blinks Red, then Orange for 1 min. Repeats
is condition persists
Inhibited
Static BP
Inverter Module Over-
temperature
Module temperature limit exceeded
Blue, MegaDySC offline
Disconnected
Mech. Bypass
MegaDySC Over-temperature
Internal temperature limit exceeded
Blue, MegaDySC offline
Disconnected
Mech. Bypass
Static Switch Failure
Open SCR(s)
Blue, MegaDySC offline
Disconnected
Mech. Bypass
Main Fuse Open
Open Fuse(s)
Blue, MegaDySC offline
Disconnected
Mech. Bypass
Enclosure Door Open
Door Open
Blue, MegaDySC offline
Disconnected
Mech. Bypass
WARNING: Dangerous voltages can still exist within the MegaDySC enclosure
even if the system is in bypass mode. Refer servicing to qualified personnel.