beautypg.com

Table 1 - operational conditions and indications, Automatic bypass switchboard operation – Rockwell Automation 1608M MegaDySC User Manual, 800 Amp - 208V User Manual

Page 26

background image

26

Rockwell Automation Publication 1608M-UM003A-EN-P - December 2013

Chapter 5

Operation

whenever the MegaDySC system is in the maintenance bypass mode (CBB
closed and CBI open).

A list of conditions and indications is given in

Table 1

. Refer to

Chapter 6

for

further information on system alarms and status display.

Table 1 - Operational Conditions and Indications

* The touchscreen will power down if both input and output voltages fall below approx. 75% of nominal

**An error message will be displayed while the red or orange text box is displayed. Refer to

Chapter 6

for further information on accessing

fault codes and status history.

Automatic Bypass
Switchboard Operation

The Automatic Bypass Switchboard consists of a bypass circuit breaker (CBB),
an input circuit breaker (CBI), and an output circuit breaker (CBO). Under
normal operating conditions raw input power is routed through CBI to the input
of the MegaDySC. The output of the MegaDySC is routed to the load through
CBO. CBB is normally open. CBB connects utility power to the load, bypassing
the MegaDySC, when operating in the maintenance bypass mode.

Refer to

page 27

for descriptions of the automatic bypass modes

CONDITION

DEFINITION

Touchscreen Display STATUS text*

INVERTER OPERATION BYPASS MODE

Normal:

88.5% < V

LINE

< 110%

Green “OK”

Standby

Static BP

Sag Event:

V

LINE

< 88.5% for less than available

runtime.

Green “OK”

Running

Inverter

Runtime Exceeded:

Cumulative runtime exceeded

Blinks Red, then Orange for 1 min. Repeats
is condition persists

Inhibited

Static BP

Normal Mode, Overload:

Load current > 110%

Red during OL condition,
Orange for 1 min. after OL ends

Inhibited

Static BP

Inverter Run Mode, Output
Overcurrent: (I

2

t)

Load current > 150% for 3 cycles

Blinks Red, then Orange for 1 min. Repeats
is condition persists

Inhibited

Static BP

Inverter Module Over-
temperature

Module temperature limit exceeded

Blue, MegaDySC offline

Disconnected

Mech. Bypass

MegaDySC Over-temperature

Internal temperature limit exceeded

Blue, MegaDySC offline

Disconnected

Mech. Bypass

Static Switch Failure

Open SCR(s)

Blue, MegaDySC offline

Disconnected

Mech. Bypass

Main Fuse Open

Open Fuse(s)

Blue, MegaDySC offline

Disconnected

Mech. Bypass

Enclosure Door Open

Door Open

Blue, MegaDySC offline

Disconnected

Mech. Bypass

WARNING: Dangerous voltages can still exist within the MegaDySC enclosure
even if the system is in bypass mode. Refer servicing to qualified personnel.