Specifications, Heat dissipation – Rockwell Automation 1204-TFB2 Terminator User Manual
Page 3
1204 Terminator (Class 1, Division 2)
3
Specifications
The following specifications are provided for the Terminator Option.
1
The drive PWM carrier frequency that you choose affects the heat dissipation and the surface temperature
of the terminator.
Heat Dissipation
This chart is based on an ambient temperature of 45 degrees C.
Category
Specifications
Input power
380-600V, Three-Phase
Maximum Drive Carrier
Frequency
1
TFA1 – 6 kHz
TFB2 – 2 kHz
Refer to “Drive Programming” on page 9 for additional information.
Ambient temperature
0-40 degrees C (32-104 degrees F)
Humidity
5-95% non-condensing
Atmosphere
Class 1, Division 2
Heat dissipation
1
Refer to the heat dissipation table below.
Enclosure type
IP65 (NEMA Type 4x)
Hazardous
Environment Rating
T3 (200
°
C); Groups A, B, C, D
Agency certification
U.L., C-UL
Altitude derating
Full rating 0-1000 meters (0-3280 feet)
Ambient
Temperature
Limit
Altitude
m
(ft)
40
30
35
0
4,000
(13,200)
3,000
(9,900)
2,000
(6,600)
1,000
(3,300)
degrees C.
Drive
Frequency
Length
meters (feet)
1204-TFA1 Terminator
1204-TFB2 Terminator
460 Volts + 10%
600 Volts + 10%
460 Volts + 10%
600 Volts + 10%
Watts
Heatsink
°
Watts
Heatsink
°
Watts
Heatsink
°
Watts
Heatsink
°
6 kHz
91 (300)
210W
142
°
C
220W
150
°
C
Must Use 2 kHz
183 (600)
250W
160
°
C
260W
169
°
C
4 kHz
91 (300)
170W
125
°
C
180W
133
°
C
183 (600)
180W
130
°
C
210W
138
°
C
2 kHz
91 (300)
80W
81
°
C
100W
95
°
C
200W
139
°
C
290W
182
°
C
183 (600)
90W
88
°
C
140W
104
°
C
250W
160
°
C
360W
200
°
C