Rockwell Automation 1204-TFB2 Terminator User Manual
1204 terminator, Instructions, Where this option is used
Instructions
Where this Option is Used
The 1204 Terminator Option can be installed in most adjustable
frequency AC drive applications to increase protection of the AC
motor. The option is designed to be used with Allen-Bradley
Adjustable frequency AC drives. When installed at the motor
terminals, the terminator can reduce potentially destructive reflected
wave spikes that can occur with long motor leads.
What this Option Contains
The Terminator Option contains the terminator device with an
attached 3 meter (10 feet) standard 4 wire 3mm
2
(12 gauge)
connection cable.
What these Instructions
Contain
These instructions contain the information you need to properly
install the Terminator Option. Recommended mounting, connecting,
and grounding procedures are included. Major topics and page
numbers are listed below.
Catalog Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Dimensions, Weights and Cable Locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Heat Dissipation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Determining the Maximum Cable Length for Your System . . . . . . . . . . . . . . . . . . . . . . . 4
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Drive Programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Catalog Number Description
The following table provides information about the catalog number
for the Terminator Option:
1
Refer to the maximum cable length tables on pages 4 through 6.
1204
– T
F
B2
First Position
Second Position
Third Position
Fourth Position
Bulletin No.
Type
NEMA Rating
Voltage Rating & Size
Description
Letter Description
Letter
Description
Code
Voltage
Rating
Drive
kW (HP)
1
Maximum
Allowable Drive
Carrier Frequency
Bulletin
Number
T
Terminator
F
NEMA Type 4
A1
380-600V 0.37-3.7
(0.5-5)
6 kHz
B2
380-600V 1.5-597
(2.0-800)
2 kHz
1204 Terminator
(Class 1, Division 2)
(Catalog Number 1204-TFA1, 1204-TFB2)
Document Outline
- Front Cover
- Where this Option is Used
- What this Option Contains
- What these Instructions Contain
- Catalog Number Description
- Dimensions, Weights and Cable Locations
- Specifications
- Determining the Maximum Cable Length for Your System
- PowerFlex 70/700/700H
- PowerFlex 700S
- Installation
- Drive Programming
- Grounding
- Maintenance
- Back Cover