beautypg.com

Rockwell Automation 1606-XLDC92D Power Supply Reference Manual User Manual

Page 11

background image

All parameters are specified at 24V, 3.8A, 24Vdc input voltage, 25°C ambient and after a 5 minutes run-in time, unless noted otherwise.

Rockwell Automation Publication 1606-RM023A-EN-P — January 2014

11

Bulletin 1606 Switched Mode Power Supplies

12. EMC

The DC/DC converter is suitable for applications in industrial environment as well as in residential, commercial and
light industry environment without any restrictions. The CE Mark indicates conformance with EMC guideline
89/336/EEC, 93/68/EEC and 2004/108/EC and the low-voltage directive (LVD) 73/23/EWG and 2006/95/EC. A detailed EMC
report is available on request.

EMC Immunity

Generic standards: EN 61000-6-1 and EN 61000-6-2

Electrostatic discharge

EN 61000-4-2

Contact discharge
Air discharge

8kV
15kV

Criterion A
Criterion A

Electromagnetic RF field

EN 61000-4-3

80MHz-2.7GHz

10V/m

Criterion A

Fast transients (Burst)

EN 61000-4-4

Input lines
Output lines

4kV
2kV

Criterion A
Criterion A

Surge voltage on input

EN 61000-4-5

+ -

1kV

Criterion A

+/- chassis ground

2kV Criterion

A

Surge voltage on output

EN 61000-4-5

+ -
+ / - chassis ground

500V
500V

Criterion A
Criterion A

Conducted disturbance

EN 61000-4-6

0.15-80MHz

10V

Criterion A

Criteria:
A: DC/DC converter shows normal operation behavior within the defined limits.
C: Temporary loss of function is possible. DC/DC converter may shut-down and restarts by itself. No damage or hazards for the DC/DC

converter will occur.

EMC Emission

Generic standards: EN 61000-6-3 and EN 61000-6-4

Conducted emission

IEC/CISPR 16-1-2, IEC/CISPR 16-2-1

Class B, input lines
(Limits for DC power ports)

Radiated emission

EN 55011, EN 55022

Class B

This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may cause undesired operation.

Switching frequency

Variable between 90kHz and 135kHz depending on load and input voltage
(output current > 0.5A)