Table 5 - System Status Description
Voltage Sag Events
A voltage sag is defined as the period when input RMS voltage drops to less than
88.5% of the rated DySC voltage. Details of each voltage sag and corresponding
ProDySC protection are captured and saved to the voltage sag log.
Voltage Sag Log
The "Voltage Sag Log" screen (See
) displays a list of the last 61 voltage
sags. Reach this screen by pressing "VOLTAGE SAGS" button on the "HOME"
screen.
Figure 17 - Voltage Sag Log
Table 6 - Voltage Sag Log Description
Description
Function
System Status
Overall system status including current operational status, availability to correct sags, and
internal cabinet temperature
Phase Status
Voltage, current, frequency, and static switch temperature are displayed for all phases. The
percentage displayed following the voltage and current is the percent of nominal value for the
ProDySC. Nominal values are listed on the “View Model Information” screen.
Waveforms
A sample of a 4 cycle waveform that includes real-time line voltage, load voltage, or load
current can be selected for display
Description
Function
#
Unique ID within the list (0-60) to identify the voltage sag
Time
Start time and date of the voltage sag
Check Mark
Denotes the ProDySC protected the voltage sag
RMS %
Worst-case RMS voltage (percent of nominal) across all phases
Duration
Duration of the voltage sag
Note: Use the up/down arrows to navigate through the list. Press the “SELECT” button to view additional details about
the voltage sag