Bypass switch wiring diagram, Figure 5 - bypass wiring diagram, Circuit breaker recommendations – Rockwell Automation 1608P ProDySC User Manual, 25 and 50 A User Manual
Page 11: Table 1 - recommended branch circuit protection, Accessing prodysc terminations, Figure 6 - knockout hole locations
Rockwell Automation Publication 1608P-UM001A-EN-P - July 2013
11
Installation
Chapter 2
Bypass Switch
Wiring Diagram
The maintenance bypass has input and output terminals labeled and located
inside the bypass enclosure as shown in
. The neutral connection is
available for 4-wire ProDySC configurations.
NOTICE: All electrical connections must be completed by a qualified electrician, in compliance
with all local codes and the National Electric Code.
Figure 5 - Bypass wiring diagram
Circuit Breaker
Recommendations
Branch circuit protection upstream of the ProDySC is required. Recommended
circuit breakers and maximum allowed circuit breaker ratings are listed in
. Branch circuit protection rated less than the ProDySC current rating
may result in nuisance tripping.
Table 1 - Recommended Branch Circuit Protection
Accessing ProDySC
Terminations
Two holes are provided for punch-out locations to provide the appropriate hole
size for conduit fittings in the ProDySC. Take care to avoid dropping any metal
filings inside the enclosure. Metallic contamination will void the product
warranty. See
for preferred Input/Output wiring locations.
Figure 6 - Knockout Hole Locations
ProDySC Rating
Recommended MCCB
Cat. No.
Max. MCCB Rating
25 A
140U-H3C3-C35
35 A
50 A
140U-H6C3-C70
70 A
2X 1.12
28
TOP VIEW