beautypg.com

Bypass switch wiring diagram, Figure 5 - bypass wiring diagram, Circuit breaker recommendations – Rockwell Automation 1608P ProDySC User Manual, 25 and 50 A User Manual

Page 11: Table 1 - recommended branch circuit protection, Accessing prodysc terminations, Figure 6 - knockout hole locations

background image

Rockwell Automation Publication 1608P-UM001A-EN-P - July 2013

11

Installation

Chapter 2

Bypass Switch
Wiring Diagram

The maintenance bypass has input and output terminals labeled and located
inside the bypass enclosure as shown in

Figure 5

. The neutral connection is

available for 4-wire ProDySC configurations.

NOTICE: All electrical connections must be completed by a qualified electrician, in compliance
with all local codes and the National Electric Code.

Figure 5 - Bypass wiring diagram

Circuit Breaker
Recommendations

Branch circuit protection upstream of the ProDySC is required. Recommended
circuit breakers and maximum allowed circuit breaker ratings are listed in

Table 1

. Branch circuit protection rated less than the ProDySC current rating

may result in nuisance tripping.

Table 1 - Recommended Branch Circuit Protection

Accessing ProDySC
Terminations

Two holes are provided for punch-out locations to provide the appropriate hole
size for conduit fittings in the ProDySC. Take care to avoid dropping any metal
filings inside the enclosure. Metallic contamination will void the product
warranty. See

Figure 6

for preferred Input/Output wiring locations.

Figure 6 - Knockout Hole Locations

ProDySC Rating

Recommended MCCB

Cat. No.

Max. MCCB Rating

25 A

140U-H3C3-C35

35 A

50 A

140U-H6C3-C70

70 A

2X 1.12

28

TOP VIEW