Scaling factors, Energy and recording interval time stamps, Frequency (register 27) – Rockwell Automation 1425 PowerMonitor Wireless 250 User Manual
Page 38

38
Rockwell Automation Publication 1425-UM001A-EN-P - January 2012
Chapter 3
Software Interface
Scaling Factors
To obtain correct metering results, divide the raw values obtained from the listed
Modbus registers by the applicable scaling factor from
and
.
Energy and Recording Interval Time Stamps
The energy counter time stamp, read from Modbus registers 24…26 and the
recording interval data time stamp, read from registers 28…29, are organized as
shown in
Frequency (register 27)
The line frequency is measured on phase 1 of the line voltage. The most recent
value measured within the recording interval is kept in this register.
Table 17 - For All PowerMonitor W250 Models Except -480 Models with External 24V DC Control Power (up to 300V AC rms)
Current
Range
100
A 200
A 500
A 1000
A 2000
A
Real Energy Wh [Intvl]
3.2
1.6
0.64
0.32
0.16
Real Energy Wh [Counter]
0.4
0.2
0.08
0.04
0.02
Reactive Energy VARh [Intvl]
3.2
1.6
0.64
0.32
0.16
Reactive Energy VARh [Counter]
0.4
0.2
0.08
0.04
0.02
Apparent Energy VAh [Intvl]
3.2
1.6
0.64
0.32
0.16
Apparent Energy VAh [Counter]
0.4
0.2
0.08
0.04
0.02
Volts
rms
25 25 25 25 25
Amperes
rms
60 30 12 6 3
Frequency,
Hz
16 16 16 16 16
Table 18 - For PowerMonitor W250 Models Ending in -480 (24V DC powered)
Current Range
100 A
500 A
2000 A
Real Energy Wh (Interval)
1.6
0.32
0.08
Real Energy Wh (Counter)
0.2
0.04
0.01
Reactive Energy VARh Interval
1.6
0.32
0.08
Reactive Energy VARh (Counter)
0.2
0.04
0.01
Apparent Energy VAh (Interval)
1.6
0.32
0.08
Apparent Energy VAh (Counter)
0.2
0.04
0.01
Voltage,
rms
12 12 12
Amperes,
rms
60 12 3
Frequency,
Hz
16 16 16
Table 19 - Time Stamp Data Syntax
Register
High Byte
Low Byte
24 28 Minute
Second
25 29 Day Hour
26 30 Year
Month